ETCR2000+ Loop Resistance Tester
Product Overview
ETCR Series Clamp Earth Resistance Tester is widely applied in ground resistance measurement, loop resistance
measurement in fields such as electric power, telecommunications, meteorology, oil field, architecture and industrial
electrical equipment, etc. C+ tester can measure the leakage current of ground wire.
ETCR Series Clamp Earth Resistance Tester measures the integrated value of ground resistance and resistance lead.
When measuring ground system with loop, there is no need to disconnect the ground wire, without auxiliary electrode,
which means safer and faster.
ETCR Series Clamp Earth Resistance Tester can measure the ground fault which can not be measured by traditional
method, can apply in the occasion where traditional methods are unworkable.
The updated ETCR Series Clamp Earth Resistance Testers have better performance: Boot up instantly, avoid boot up
errors; More reliable battery cover, convenient to change battery; Wider range, larger memory;
Optional RS232 interface, available to transfer data to PC and generate report files, easy to analyze or backup data.
Key Features
Spec
Function | Ground resistance test, Loop resistance test |
Power Supply | 6VDC 4 PCS of AA Alkaline batteries |
Resistance Range | 0.01-1200Ω |
Resistance Resolution | 0.001Ω |
Highest Resistance Accuracy | ±1%±0.01Ω |
Data memory | 99 Sets |
Alarm Threshold Setting Range | Resistance: 1-199Ω |
Alarm Sound and Light | “Beep-beep-beep” alarm tone, Alarm Symbol Flashing, Press AL key to turn on, turn off Alarm or set Alarm Threshold. |
Interference Signal Recognition | “Beep-beep-beep” tone, NOISE symbol blinking |
Working Temperature and Humidity | -20℃-55℃;20%RH-90%RH |
LCD Screen | 4 Digits LCD display, Screen L×W: 47mm×28.5mm |
Clamp Size | 65mm×32mm |
Clamp Opening Extent | 32mm |
Clamp Dimension | L×W×T: 285mm×85mm×56mm |
Protection Level | Dual Insulation |
Structural Feature | Clamp CT |
Shifting | Automatic shifting |
External magnetic field | <40A/m |
External electrical field | <1V/m |
Single measurement time | 0.5 second |
Resistance measurement frequency | >1KHz |
Measured current frequency | 50/60Hz Automatic measurement |
Low Battery Indication | Low battery symbol displays when battery is lower then 5.3V |
Memory Full Indication | MEM symbol blinks when all 99 sets memory is full |
Over Range Indication | Out of range indication “OLΩ”, “L0.01” or “OL A” |
Auto Power-off | 5 minutes after Boot up |
Power Consumption | Max 50mA either in booting up or normally working, Continuously working for 30 hours |
RS232 Interface (Optional) | The data stored in the meter are uploaded to the computer through RS232 interface and data wire, Then generate report files |
Safety Provisions | IEC1010-1, IEC1010-2-032, Pollution level 2, CAT Ⅲ(150V) |